Notice: Function WP_Scripts::add was called incorrectly. The script with the handle "ekit-behance-feed-script-handle" was enqueued with dependencies that are not registered: elementor-editor. Please see Debugging in WordPress for more information. (This message was added in version 6.9.1.) in /home/ixmnbnch7gbd/public_html/wp-includes/functions.php on line 6131
For standby use (Trickle charge or float charge )
Charge the battery at a constant voltage of 2.275V/Cell (27°C). When charging at an ambient temperature of 5°C or below or 35°C or above, it is necessary to adjust the charge voltage in relation to the temperature. The temperature coefficient should be ± 4mV/°C cell (+ if temperature is lower and – if temperature is higher).
Initial charge current should be 0.20CA (where C is the nominal capacity value and A is amperes) or less.
Charge the battery as an ambient temperature from 5°C to 35°C to prevent any adverse effects on its effective life.
For cyclic use
Charge the battery at a constant voltage of 2.275V/Cell (27°C). When charging at an ambient temperature of 5°C or below or 35°C or above, it is necessary to adjust the charge voltage in relation to the temperature. The temperature coefficient should be ± 4mV/°C cell (+ if temperature is lower and – if temperature is higher).
Initial charge current should be 0.20CA (where C is the nominal capacity value and A is amperes) or less.
Charge the battery as an ambient temperature from 5°C to 35°C to prevent any adverse effects on its effective life.